CGM 180 P
Industrial Power Generator
400 V - 198 kW
7010 cc - 210.4 HP
DIESEL
CGM 180 P - Industrial Power Generator 198 kW (kVA)
CGM 180P is a fixed professional generator at 400V in the open and closed versions. Generator 198 kW (kVA) is a professional CGM generator suitable for continuous industrial use .
Functional specifications
Professional generator 198 kW
CGM 180P is a fixed industrial generator with continuous net power of 144 kW (180 kVA) . With PERKINS 1106A-70TAG3 engine with mechanical speed governor , 210.4 HP and 7010 cc at 1500 RPM . CGM 180 P has 6 cylinders , with water aspiration and cooling .
AVR Voltage Regulator
CGM 180 P is equipped with a 4-pole AVR voltage regulator with voltage accuracy of +-1%. Brushless alternator .
Manual electrical panel
Equipped with a control unit with Comap InteliLite 9 multimeter , this electrical panel has IP44 protection. With standard emergency button and magnetothermal protection switch .
Standard control unit
The standard control unit is equipped with automatic/manual start , remote start , periodic test , with multimeter , counter , battery and backlit LCD display . A USB port is present. Communication accessories available.
Soundproof cabin for outside
The soundproof version is equipped with a soundproof and weatherproof cabin, made of structural steel sheet , thickness between 1.5 and 4.5 mm. Epoxy powder coating RAL5015 textured . Internal lining in sound-absorbing material with high noise reduction , finished with water-repellent and anti-oil material.
CGM 180P has maximum accessibility for ordinary and extraordinary maintenance by means of two large doors with key lock and padlocks.
Fresh air intake from below and on the short side, hot air exhaust from above and below the cabin.
Details
Lifting hooks
Feet for stable support
Available models
Two versions can be selected from the drop-down menu:
- CGM 180P open
- CGM 180P soundproof (silenced)
Characteristics
- Fixed generator 198 kVA (158.4 kW)
- Open and closed version
- Powerful 7010cc engine at 210.4 HP / 157 kW
- Diesel generator
- Stamford Alternator - Marelli
- Quiet 69 dB(A)
- Manual electrical panel
- ATS panel for network failure
Main Options
- 400 A Automatic Mains-Generation Transfer Switchboard (ATS)
- 120 L enlarged tank with containment basin
- Engine preheater 1000 W
- Electronic RPM regulator
- Automatic fuel transfer kit with manual by-pass system
- Differential switch
- Electric tank float for fuel level monitoring from the electronic control unit
- Oil pressure and engine cooling water temperature measuring instruments
Technical Data
Power Supply | Three-phase |
Motor | PERKINS 1106A-70TAG3 |
Speed governor | Mechanical |
Engine revolution | 1500 RPM |
Maximum Power | 198 KVA - 158.4 KW cos φ 1 |
Continuous power | 180 KVA - 144 KW cos φ 1 |
No. of Cylinders | 6 |
Aspiration | Natural |
Cooling | Waterfall |
Cylinder capacity | 7010cc |
Bore x stroke | 105 x 135 mm |
Fuel | Diesel |
Consumption | 8.1 h - 18.8÷39.6 L/h |
Standard Tank Capacity | 250 L |
Continuous Power | 210 HP - 157 kW |
Alternator | Stamford-Marelli |
Voltage Regulation | AVR |
Voltage Precision | 1% |
No. of Poles | 4 |
Noise at 7 m | 69dB(A) |
Exhaust Diameter | 114mm |
Electrical System Voltage | 12V |
Insulation Class | H |
Overtemperature Class | H |
Open Generator Size | 240 x 110 x 200 cm |
Open Generator Weight | 1740 kg |
Soundproof Generator Size | 320 x 110 x 209 cm |
Soundproof Generator Weight | 2070 kg |
Technical Data
Power Supply | Three-phase |
Motor | PERKINS 1106A-70TAG3 |
Speed governor | Mechanical |
Engine revolution | 1500 RPM |
Maximum Power | 198 KVA - 158.4 KW cos φ 1 |
Continuous power | 180 KVA - 144 KW cos φ 1 |
No. of Cylinders | 6 |
Aspiration | Natural |
Cooling | Waterfall |
Cylinder capacity | 7010cc |
Bore x stroke | 105 x 135 mm |
Fuel | Diesel |
Consumption | 8.1 h - 18.8÷39.6 L/h |
Standard Tank Capacity | 250 L |
Continuous Power | 210 HP - 157 kW |
Alternator | Stamford-Marelli |
Voltage Regulation | AVR |
Voltage Precision | 1% |
No. of Poles | 4 |
Noise at 7 m | 69dB(A) |
Exhaust Diameter | 114mm |
Electrical System Voltage | 12V |
Insulation Class | H |
Overtemperature Class | H |
Open Generator Size | 240 x 110 x 200 cm |
Open Generator Weight | 1740 kg |
Soundproof Generator Size | 320 x 110 x 209 cm |
Soundproof Generator Weight | 2070 kg |
INDORS is an Authorized Service and Repair Center
Our workshop is able to guarantee efficient and professional repairs: speed; of intervention, competence and availability are our strengths.
By purchasing from Indors you will also have purchased peace of mind: our Assistance and Repairs Service guarantees quick and timely solutions for any problem thanks to the safe availability; of spare parts, your equipment will always be efficient and available within a few days at a low cost. More information
EU Warranty 2 Anni
All products sold by Indors are covered by a legal guarantee of 2 years from the date of purchase for purchases by individuals (12 months for professional users) for lack of conformity, pursuant to art. 128 ff. Legislative Decree no. 206/2005.
More information